Figure 62: Example characteristic
Non-directional earth fault current protection
Procedure
1. Measure that the operate current is equal to the INNonDir> setting.
The function activates the START and STDIRIN output.
2. Measure the operate time of the timer by injecting a current to get two times
the set INNonDir> operate value.
3. Compare the result with the expected value.
The expected value depends on whether definite time tINNonDir or inverse
time was selected.
4. Continue to test another function or complete the test by setting the test mode
to Off.
Residual overvoltage release and protection
Procedure
1. Measure that the operate voltage is equal to the UN> setting.
The function activates the START and STUN signals.
2. Measure the operate time by injecting a voltage 1.2 timers set UN> operate
value.
3. Compare the result with the set tUN operate value.
4. Inject a voltage 0.8 · UNRel> and a current high enough to operate the
directional function at the chosen angle.
5. Increase the voltage until the directional function is released.
6. Compare the measured value with the set UNRel> operate value.
Section 13 1MRK 504 088-UEN C
Verifying settings by secondary injection
144
Installation and commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals