L1
(A)
L2
(B)
L3
(C)
Protected Object
CT 1500/5
Star/Wye
Connected
7
8
9
10
11
12
1
2
3
4
5
6
AI01 (I)
AI02 (I)
AI03 (I)
AI04 (I)
AI05 (I)
AI06 (I)
6
7
8
IED
X1
R
1
1
2
4 5
U
R
2
1
3
4
2
1 2 3
N
1-Ph Plate with Metrosil and Resistor
2
3
5
4
9
N
L1
(A)
L2
(B)
L3
(C)
C
T
1
5
0
0
/
5
1
IEC07000194_2_en.vsd
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI2
BLOCK
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
TYPE
IEC07000194 V2 EN
Figure 29: CT connections for restricted earth fault protection
Pos Description
1 Scheme earthing point
Note that it is of outmost importance to insure that only one earthing point
exist in such scheme.
2 One-phase plate with setting resistor and metrosil.
3 Necessary connection for the metrosil. Shown connections are applicable for both types of one-
phase plate.
4 Position of optional test switch for secondary injection into the high impedance differential IED.
5 Necessary connection for setting resistor. Shown connections are applicable for both types of
one-phase plate.
6 How to connect REFPDIF high impedance scheme to one CT input in IED.
7 Transformer input module where this current input is located.
Note that the CT ratio for high impedance differential protection application
must be set as one.
For main CTs with 1A secondary rating the following setting values shall be entered:
CTprim
=
1A
and
CTsec
=
1A
For main CTs with 5A secondary rating the following setting values shall be entered:
CTprim
=
5A
and
CTsec
=
5A
The parameter
CTStarPoint
shall always be left to the default value
ToObject
1MRK 504 088-UEN C Section 5
Installing the IED
57
Installation and commissioning manual