ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 205
No.
Functionality
Name
Data Point
Type (DPT)
Length
Flags
C
R
W
T
U
50
Switch speed
Fan EFG (Multi-level)
5.001
1 byte
x
x
Switch speed
Fan EFG (Multi-level)
5.010
1 byte
x
x
Switch
Output E
1.001
1 bit
x
x
51
Switch speed 1
Fan EFG (Multi-level)
1.001
1 bit
x
x
Switch
Fan EFG (One-level)
1.001
1 bit
x
x
Permanent on
Output E
1.003
1 bit
x
x
52
Switch speed 2
Fan EFG (Multi-level)
1.001
1 bit
x
x
Disable function Time
Output E
1.003
1 bit
x
x
53
Switch speed 3
Fan EFG (Multi-level)
1.001
1 bit
x
x
Status Switch
Output E
1.001
1 bit
x
x
x
54
Fan speed up/down
Fan EFG (Multi-level)
1.007
1 bit
x
x
55
Status Fan ON/OFF
Fan EFG
1.001
1 bit
x
x
x
56
Status Fan speed
Fan EFG (Multi-level)
5.010
1 byte
x
x
x
57
Status Fan speed 1
Fan EFG (Multi-level)
1.001
1 bit
x
x
x
58
Status Fan speed 2
Fan EFG (Multi-level)
1.001
1 bit
x
x
x
59
Status Fan speed 3
Fan EFG (Multi-level)
1.001
1 bit
x
x
x
60
Switch
Output F
1.001
1 bit
x
x
Run-on
Fan EFG (Multi-level)
1.003
1 bit
x
x
61
Limitation 1
Fan EFG
1.003
1 bit
x
x
Permanent on
Output F
1.003
1 bit
x
x
62
Limitation 2
Fan EFG
1.003
1 bit
x
x
Disable function Time
Output F
1.003
1 bit
x
x
63
Limitation 3
Fan EFG
1.003
1 bit
x
x
Status Switch
Output F
1.001
1 bit
x
x
x
64
Limitation 4
Fan EFG
1.003
1 bit
x
x
65
Forced operation
Fan EFG
1.003
1 bit
x
x
66
Automatic ON/OFF
Fan EFG
1.003
1 bit
x
x
67
Status Automatic
Fan EFG
1.003
1 bit
x
x
x
68
Status byte fan
Fan EFG
Non DPT
1 byte
x
x
x
69
Control value A
Fan EFG (2 control values)
5.010
1 byte
x
x
Actuating value
Fan EFG (only 1 control
value)
5.010
1 byte
x
x
70
Control value B
Fan EFG (2 control values)
5.010
1 byte
x
x
Switch
Output G
1.001
1 bit
x
x
71
Toggle control value A/B
Fan EFG (2 control values)
1.001
1 bit
x
x
Permanent on
Output G
1.003
1 bit
x
x
72
Fault control value
Fan EFG
1.005
1 bit
x
x
x
Disable function Time
Output G
1.003
1 bit
x
x
73
Status Switch
Output G
1.001
1 bit
x
x
x
74…
79
Not assigned