EasyManua.ls Logo

ABB tacteo KNX - Object Type

ABB tacteo KNX
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description of application and parameters
Application "General functions"
Product manual 2CKA001473B9482
164
11.6.7.2 Object type
Options: 1-bit switching
1-bit travel
1-bit stop/adjust
1 byte 0 - 100%
1 byte 0 - 255
2-byte float
2-byte signed
2-byte unsigned
4-byte float
4-byte signed
4-byte unsigned
1-bit switching:
The value is sent as 1-bit switching commands (0 or 1), e.g. On/Off, enabled/blocked,
true/untrue.
1-bit travel:
The value is sent as 1-bit switching commands, e.g. travel up or down.
1-bit stop/adjust:
The value is sent as 1-bit switching commands, e.g. travel stop, adjust slats.
1 byte 0 - 100%:
The value is sent as 1-byte value without a sign (percentage value).
(0 = 0%, 255 = 100%)
1 byte 0 - 255:
The value is sent as 1-byte value without a sign. Any value 0 - 255.
2-byte float:
The value is sent as floating point value (-671088.6 - 670760.9), e.g. temperature or
moisture value.
2-byte signed:
The value is sent as 2-byte value with a sign, (-32768 - +32767), e.g. time difference or
percentage difference.
2-byte unsigned:
The value is sent as 2-byte value without a sign (0 - 65535), e.g. time or brightness
value.
4-byte float:
The value is sent as 4-byte floating point value (-4000000 to 4000000), physical values,
e.g. luminosity, electric power, pressure.
4-byte signed:
The value is sent as 4-byte value with a sign (-2147483648 - 2147483647), e.g.
counting impulse, time difference.
4-byte unsigned:
The value is sent as 4-byte value without a sign (0 - 4294967295), e.g. counting
impulse.
The set option fixes the bit size of the input and output object.

Table of Contents