Description of application and parameters
Application "Function block RTC"
Product manual 2CKA001473B9482
138
11.5.138.16 Alarm function
Options: Deactivated
Activated
Deactivated:
Communication object "Alarm" is not enabled.
Activated:
Communication object "Alarm" is enabled.
The 1-byte communication object "Alarm" can be enabled with this parameter. If an On telegram
is received via the object, the LED of the button flashes. If an Off telegram is received via the
object, the LED lights up continuously.
The LED flashes in the colour that is set for the status or function illumination. If object
"Day/night mode" is enabled, the LED flashes either bright or dark.
The alarm function can, for example, display a wind alarm or an open door when the user wants
to lower a Blind or a roller blind.
Note
The parameter is available via the following settings:
The parameter is set on "Status illumination".
and
Parameter "Object type for status object" is set on "1 bit".
and
Parameter "Colour for Off" is set on a colour and not on "Off".
and
Parameter "Colour for On" is set on a colour and not on "Off".
The parameter is available also via the following settings:
The parameter is set on "Status illumination".
and
Parameter "Object type for status object" is set on "1 byte 0-100%.
and
All parameters "Colour for zone x" are set on a colour and not on "Off".
The parameter is available also via the following settings:
The "Operating mode" parameter is set on "Function illumination".
and
Parameter "Colour for function illumination" is set on a colour and not on
"Off".