EasyManuals Logo

ABB tacteo KNX User Manual

ABB tacteo KNX
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #149 background imageLoading...
Page #149 background image
ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 147
Run-on behavior
Options:
No
Yes
This parameter activates a run-on for the fan. If the fan changes to a lower speed, it remains in the
previous speed for the parameterized run-on time and only then reduces the speed by one level.
If the fan goes through several speed changes, run-on times are executed successively, adding on those
times.
A run-on time of 0 seconds means that run-on is deactivated.
Run-on is executed regardless of where the speed change originates (automatic operation, direct
operation, manual procedure, fan switch off).
Selection of option Yes:
Dependent parameters:
Run-on times speed 3
in s [0...65,535]
Options:
0…20…65,535
Run-on times speed 2
in s [0...65,535]
Options:
0…20…65,535
Run-on times speed 1
in s [0...65,535]
Options:
0…20…65,535