ABB i-bus
®
KNX
Commissioning
110 2CDC508134D0202 | FCA/S 1.x.x.1
Reaction after bus voltage recovery
Options:
Unchanged
Select
This parameter determines the reaction of the output at bus voltage recovery.
Unchanged: The last valve control is restored.
Select: A value is determined. Active priorities override the parameterized control.
Dependent parameter:
Control value in % [0...100]
Options:
0…100
This parameter determines the control of the output after bus voltage recovery in %.