Description of application and parameters
Application "Function block RTC"
Product manual 2CKA001473B9482
108
11.5.85 Setpoint settings — Set-point temperature for frost protection (°C)
Options: Setting option between 5 - 15
Function for protecting the building against the cold. On devices with a display, this mode is
indicated by the frost protection icon. Manual operation is blocked.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating", "Heating with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
11.5.86 Setpoint settings — Setpoint temperature for cooling comfort (°C)
Options: Setting option between 10 - 40
Specifies the comfort temperature for cooling when people are present.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling" or "Cooling with additional stage".
11.5.87 Setpoint settings — Increase for standby cooling (°C)
Options: Setting option between 0 - 15
Specifies the temperature in cooling mode when nobody is present. On devices with a display,
this mode is indicated by the standby icon.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
11.5.88 Setpoint settings — Increase for ECO cooling (°C)
Options: Setting option between 0 - 15
Specifies the temperature in cooling mode when nobody is present. On devices with a display,
this mode is indicated by the eco icon.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".