ABB tacteo KNX - Basic Stage Heating - Control Value Difference for Sending of Heating Control Value; Basic Stage Heating - Cyclic Sending of the Control Value (Min); Basic Stage Heating - PWM Cycle Heating (Min)

ABB tacteo KNX
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description of application and parameters
Application "Function block RTC"
Product manual 2CKA001473B9482
85
11.5.23 Basic stage heating — Control value difference for sending of heating control value
Options: 2 %
5 %
10 %
Send cyclic only
The control values of the 0 - 100% PI continuous controller are not transmitted after every
calculation. Instead, they are transmitted when the calculation results in a value that is different
enough to the previous sent value to make a transmission meaningful. This value difference can
be entered here.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil".
11.5.24 Basic stage heating — Cyclic sending of the control value (min)
Options: Setting option between 1 - 60 minutes
The current control value used by the device can be cyclically transmitted to the bus.
Note
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On", "2-point 1 Byte, 0/100%", "PI continuous, 0-
100%" or "Fan coil".
11.5.25 Basic stage heating — PWM cycle heating (min)
Options: Setting option between 1 - 60 minutes
In PI PWM, On/off the control value percentage values are converted into a pulse-interval
signal. This means that a selected PWM cycle will be divided into an on-phase and an off-phase
based on the control value. Accordingly, a control value output of 33% in a PWM cycle of 15
min. results in an "On-phase" of five minutes and an "Off-phase" of 10 min. The time for a PWM
cycle can be specified here.
Note
This parameter is only available when the "Control value type" parameter is set
on "PI PWM, On/Off“.

Table of Contents

Related product manuals