ABB i-bus
®
KNX
Commissioning
96 2CDC508134D0202 | FCA/S 1.x.x.1
Parameter window Enable output A...D Fan Coil Actuator, 0...10 V
Output A
Options:
Disabled
Valve drive, analog (0...10 V)
This parameter defines the individual operation mode of the output.
Disabled: No operation mode selected.
Valve drive, analog (0...10 V): The parameter (window) and communication objects for the operation
mode Valve drive, analog (0...10 V) are enabled.
Valve control output A
0…10 V
Valve voltage on bus voltage failure
0 volts
This also applies for output C.
Assignment of the valves
Note
Outputs A and C are automatically assigned via the selection in the parameter Fan Coil operating mode.