ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 135
Hysteresis is only taken into account in automatic operation
Note
Hysteresis threshold
value in % +/- [0...20 %]
Options:
0…5…20
This sets a hysteresis at which switchover to the next fan speed occurs. The hysteresis applies for all three
threshold values.
The setting 0 causes immediate switching without hysteresis.
The entered percentage value is directly added to or subtracted from the percentage value of Threshold
value speed x. The result is a new upper or lower threshold value.
Switch threshold top (switch on) = threshold value + hysteresis
Switch threshold bottom (switch off) = threshold value - hysteresis