EasyManuals Logo

ABB tacteo KNX User Manual

ABB tacteo KNX
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #103 background imageLoading...
Page #103 background image
ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 101
Cycle time of PWM
in s [10...6,000]
Options:
10180…6,000
For setting the cycle time for the pulse width modulation.
If the control value is received via a 1 bit value, this parameter serves as the basis for calculation of the
control of the output with
Bus voltage failure/recovery
Forced operation
Fault of the control value (control fault)
Characteristic correction
Opening time of valve drivein s [10...6,000]
Options:
10180…6,000
With this parameter, a time is set in seconds that the connected valve requires to move from position 0%
(valve closed) to position 100% (valve fully open).
Note
The time should be taken from the technical data of the valve, and it corresponds with the total runtime.
Closing time of valve drivein s [10...6,000]
Options:
10180…6,000
With this parameter, a time is set in seconds that the connected valve requires to move from position
100% (valve open) to position 0% (valve fully closed).
Note
The time should be taken from the technical data of the valve, and it corresponds with the total runtime.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB tacteo KNX and is the answer not in the manual?

ABB tacteo KNX Specifications

General IconGeneral
BrandABB
Modeltacteo KNX
CategoryController
LanguageEnglish

Related product manuals