EasyManua.ls Logo

ABB tacteo KNX - Object Type; Number of Input Objects

ABB tacteo KNX
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description of application and parameters
Application "General functions"
Product manual 2CKA001473B9482
170
11.6.8.2 Object type
Options: 1 byte 0 - 100%
1 byte 0 - 255
2-byte float
2-byte signed
2-byte unsigned
4-byte float
4-byte signed
4-byte unsigned
1 byte 0 - 100%:
The value is sent as 1-byte value without a sign (percentage value).
(0 = 0%, 255 = 100%)
1 byte 0 - 255:
The value is sent as 1-byte value without a sign. Any value 0 - 255.
2-byte float:
The value is sent as floating point value (-671088.6 - 670760.9), e.g. temperature or
moisture value.
2-byte signed:
The value is sent as 2-byte value with a sign, (-32768 - +32767), e.g. time difference or
percentage difference.
2-byte unsigned:
The value is sent as 2-byte value without a sign (0 - 65535), e.g. time or brightness
value.
4-byte float:
The value is sent as 4-byte floating point value, physical values, e.g. luminosity, electric
power, pressure.
4-byte signed:
The value is sent as 4-byte value with a sign (-2147483648 - 2147483647), e.g.
counting impulse, time difference.
4-byte unsigned:
The value is sent as 4-byte value without a sign (0 - 4294967295), e.g. counting
impulse.
The set option fixes the bit size of the input and output object.
11.6.8.3 Number of input objects
Options: Setting option from 1 to 8
The parameter is used to set the number of input telegrams to be compared with each other.

Table of Contents

Related product manuals