Description of application and parameters
Application "Function block RTC"
Product manual 2CKA001473B9482
84
11.5.19 Basic stage heating
Note
Only available when the "Extended settings" parameter under "Heating control"
is set on "Yes".
11.5.20 Basic stage heating — Status object heating
Options: No
Yes
– This parameter enables the "Status heating" communication object.
11.5.21 Basic stage heating — Mode of the control value
Options: Normal
Inverse
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
– N
ormal
: Value 0 means "Valve closed".
–
Inverse
: Value 0 means "Valve open".
11.5.22 Basic stage heating — Hysteresis (x 0.1°C)
Options: Setting option between 3 - 255
The hysteresis of the two-point controller specifies the fluctuation range of the controller around
the setpoint value. The lower switching point is located at "Setpoint value minus hysteresis" and
the upper point is at "Setpoint value plus hysteresis".
Note
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On" or "2-point 1 Byte, 0/100%".