ABB i-bus
®
KNX
Commissioning
74 2CDC508134D0202 | FCA/S 1.x.x.1
Enable communication object
"Status Man. operation" (1-bit)
Options:
No
Yes
Yes: The 1-bit communication object Status Man. operation is enabled.
Dependent parameter:
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only: The status is updated but not sent.
On change: The status is sent when a change occurs.
After request: The status is sent when a request occurs.
After a change or request: The status is sent on a change or a request.
For further information see: Manual operation, p. 61
Function of the buttons:
Output A/B blocked
Output C/D blocked
Output E (speed 1) blocked
Output F (speed 2) blocked
Output G (speed 3) blocked
Input a, b, c
Note
The functions Fan speed x output x blocked only appear if the option Enabled as fan has been selected
for the parameter Outputs E, F, G in the parameter window Enable output E...H.