ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 219
No.
Functionality
communication object name
Data type
Flags
61
Limitation 1
Fan E, F, G
1 bit
DPT 1.003
C, W
This communication object is enabled if the parameter Enable limitations has been selected with the option Yes in Parameter
window Automatic control (Multi-level), p. 137.
Note
Limitation 1 is only active in automatic operation.
The limitation 1 is active if a telegram with the value 1 is received on the communication object Limitation 1. The Limitation 1
is deactivated if a telegram with the value 0 is received on the communication object Limitation 1.
When Limitation 1 is activated, the fan can only assume the fan speed or speed range as set in the parameter Limitation 1.
Telegram value:
0 = Limitation x inactive
1 = Limitation x active
62
Limitation 2
See communication object 61
63
Limitation 3
See communication object 61
64
Limitation 4
See communication object 61