FCA/S 1.x.x.1 | 2CDC508134D0202 219
communication object name
This communication object is enabled if the parameter Enable limitations has been selected with the option Yes in Parameter
window Automatic control (Multi-level), p. 137.
Limitation 1 is only active in automatic operation.
The limitation 1 is active if a telegram with the value 1 is received on the communication object Limitation 1. The Limitation 1
is deactivated if a telegram with the value 0 is received on the communication object Limitation 1.
When Limitation 1 is activated, the fan can only assume the fan speed or speed range as set in the parameter Limitation 1.
0 = Limitation x inactive
1 = Limitation x active
See communication object 61
See communication object 61
See communication object 61