ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 227
No.
Functionality
communication object name
Data type
Flags
69
Control value A
(if 2 control values) or
Control value
(if only 1 control value)
Fan E, F, G
1 byte
DPT 5.010
C, W
This communication object is enabled if automatic operation has been enabled in Parameter window E, F, G: Fan (One-
level), p. 149.
Using this communication object the control value for automatic operation is predefined as a 1 byte value [0...255].
70
Control value B
(if 2 control values)
Fan E, F, G
1 byte
DPT 5.010
C, W
This communication object is enabled if automatic operation has been enabled in Parameter window E, F, G: Fan (One-
level), p. 149, and two inputs have been activated by the parameter Number of control value inputs in Parameter window
Automatic control (One-level), p. 156.
Using this communication object the second control value for automatic operation is predefined as a 1 byte value [0...255].
71
Toggle control value A/B
(if 2 control values)
Fan E, F, G
1 bit
DPT 1.001
C, W
This communication object is enabled if two communication objects have been activated for the control values (control value
A and control value B) in Parameter window Automatic control (One-level), p. 156, and they are to be selected by a
communication object.
72
Fault control value
Fan E, F, G
1 bit
DPT 1.005
C, R, T
This communication object is enabled if the parameter Activate monitoring control values has been selected with the option
Yes in Parameter window Automatic control (One-level), p. 156.
This communication object displays control value faults.
The blower actuator uses the Fault control value communication object to report a fault and then reacts according to the
parameterization for faults.
Telegram value:
0 = No fault
1 = Fault
Note
If no value is sent to the communication object Control value A, Control value B or Control Value for a set time, a
sender fault is assumed. If the communication object Toggle control value A/B receives a value, the monitoring time
is started.
73…79
Not assigned