- 76 -
000026GG
5 - Installation
3. MULTICONTACT MC4 quick-t connectors
Installation of Multicontact MC4 connectors requires crimping to be carri-
ed out with suitable equipment.
- Strip the cable to which you want to apply the connector (after verifying
that it complies with the connector limits).
- Apply the terminal to the conductor using the designated pliers.
Multi-Contact 32.6020-19100
- Insert the cable with the terminal into the interior of the connector, until
you hear the click indicating that the terminal is locked inside the con-
nector.
Click
- Firmly tighten the cable gland using the relevant tool to nish the ope-
ration.
2.5 Nm
Multi-Contact
32.6024
12mm
4...6mm
5.5...9mm
2