- 98 -
000541CG
7 - Operation
- Watch for the green LED to stop ashing remain ON if when self-tests
and grid checks are complete and the inverter starts production.
Any conguration of the inverter must be carried out
through Aurora Manager LITE software. The software and its
own manual are available at www.abb.com/solarinverters.
Possible LEDs behaviour are described in the following paragraph.
Enabling and default parameters
These main parameters are preset by the Manufacturer and can be
modied using the Aurora Manager Lite software.
Date and time: It is set to UTC (daylight saving time is NOT considered).
• RS485 address:
RS485 (1) default setting on AUTO
RS485 (2) default setting on AUTO
• Vstart: 420 V
• Congurable relay (ALARM): default setting on “PRODUCTION”
• Remote control: OFF
• UV Protection Time: 60 sec.
• Reactive power: NO regulation.
MPPT scan: ON (active) allows maximum power point tracking to be
carried out.
• Power reduction: 100%. No power limit activated.