100
AcuRev 1300
Programming record
Table 5-24 Programming record address
Modbus address
Parameter
description
Data
type
R/W Data range Default Model
Register
number
HEX Decimal
1A00H-
1A01H
6656-
6657
total
programming
time
Dword R 0-999999
2~4
2
last time programming record
1A02H-
1A04H
6658-
6660
occur time word R YYMMDDhhmmss
2~4
3
1A05H 6661 programming
event ag
word R
2~4
1
last 2
nd
time –last 3
rd
time
1A06H-
1A0DH
6662-
6669
2~4
8
Note*:
System Event Marking:
01: Meter Address Change 02: RS485 Parameter Change (including Baud Rate and Parity bit setting )
03: Energy Pulse Setting 04: Demand Parameter Setting(calculation method, demand period,
slipping time) 05: Reactive power calculation method 06: VAR/PF Convention 07: Date and Time
Setting 08: Measure side change 09: Wiring Mode 10: CT or PT change 11: Pulse Constant and
Pulse Width 12: Decimal Digits 13: RO Output Mode 14: Alarm Setting Parameter
100: Energy Value Base 101: TOU Parameter Setting
102: Daylight Saving Time 103: Trend Record
104: Alarm set parameters change
Demand clearance event
Table 5-25 Demand clearance address
Modbus address
Parameter
description
Data
type
R/W Data range Default Model
Register
number
HEX Decimal
1B00H-
1B01H
6912-6913
Total Times
of Demand
Reset
word R 0~0xFFFFFFFF 2~4 2
last time demand clearance record