45
AcuRev 1300
segment table. The rate parameter is one of 0,1,2,3(0:sharp; 1:peak; 2:valley; 3:even).
6. Holiday setting: the number of holiday is integer from 0-30, after finishing the
setting, it would be holiday setting, which format is xx month-xx date.
Note: User can customarize the factory settings of time zone segment. When no
asking, the meter would be set as the default factory settings. Users can recover the time
zone segment setting value to the default value through communication.
The use of TOU energy holidays: in the TOU energy parameter setting part, rstly we
should set the number of holidays, then set the demanded holiday in the holiday setting
bar, the format is xx month- xx date. At this time, through setting the meter operate time,
when the meter’s operation time is in the setting time, the energy would increase under
the corresponding rate.
Note: time-division energy is with the highest priority on holidays, when the set of
special date is valid, the measurement of energy would consider the holidays at rst.
Weekly restfunction
The use of TOU energy weekly rest: weekly rest(bit0- Sunday; bit1-bit6: Monday-
Saturday . when bit is 1, it means weekday, when bit is 0 , it means weekend.) through
setting the clock, when the meter’s clock is under the weekly rest time segments, the
energy would increase under the corresponding rate.
b)The value of the currentrate of self-communication order.
Daylight Saving Time function
Under the DST enable condition, if we choose xed date option, it would change the
DST according to the xed date setting format. The format is month/date/hour/minute/
adjust time(unit:min). if we choose unxed date option, it would change the DST according
to the unxed date setting format.The format is month/ week/which week/hour/minute/