AcuRev 1300
704H 1796 Pulse Output Time word R/W 50~3000ms
(valid with Pulse
Output Mode)
1000 2~4 1
Alarm Parameter Setting for the 1st group
705H 1797 Parameter Number Word R/W 0~28 (please see
appendix “Alarm
Parameters
comparison
table”)
0 2~4 1
706H 1798 Comparing Method Word R/W 0: larger; 1:
equal; 2: less
0 2~4 1
707H 1799 Setpoint Value Word R/W 0 2~4 1
708H 1800 Delay Time Word R/W 0~3000 (×10ms) 0 2~4 1
Alarm Parameter Setting for the 2nd 12th group
709H-
73BH
1801-
1851
The same as above word R/W 2~4 44
Table 5-21 SunSpec System Information Address
Modbus address
Parameter
description
Data
type
R/W Data range Default Model
Register
number
HEX Decimal
1000H-
1001H
4096-
4097
SunSpec_ID Uint16 R 0x53756e53 1 1~4 2
1002H 4098 ID Uint16 R 1 1 1~4 1
1003H 4099 Lenth Uint16 R 65 65 1~4 1
1004H-
1013H
4100-
4115
Manufacturer string R
Well known
value registered
with SunSpec for
compliance
Accuenergy 1~4 16
1014H-
1023H
4116-
4131
Model string R
Manufacturer
specic value (32
chars)
AcuRev1300 1~4 16