55
AcuRev 1300
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
Reserve Phase
Voltage A
Missing
Phase
Voltage B
Missing
Phase
Voltage C
Missing
Reserve Phase
Voltage
A wrong
Connecting
Phase
Voltage
B wrong
Connecting
Phase
Voltage
C wrong
Connecting
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
Reserve Phase
Current
A Wrong
Direction
Phase
Current
B Wrong
Direction
Phase
Current
C Wrong
Direction
Reserve Phase
Current
A Wrong
Connecting
Phase
Current
B Wrong
Connecting
Phase
Current
C Wrong
Connecting
Can also through the LCD to display test results:
The first screen in the entire information mode voltage test results, the format for
"UXXXXXX",Where X represents the number "1" or "0", "0", said the incident was not
happened ; "1", said the incident was happened.
From left to right 1 ~ 3 digits said Phase Voltage A Missing, Phase Voltage B Missing ,
Phase Voltage C Missing, 4 ~ 6 said Phase Voltage A wrong Connecting, Phase Voltage B
wrong Connecting,Phase Voltage C wrong Connecting.
The second screen in the entire information mode voltage test results, the format
for "IXXXXXX",Where X represents the number "1" or "0", "0", said the incident was not
happened; "1", said the incident was happened.
From left to right 1 ~ 3 digits said Phase Current A Wrong Direction,Phase Current B
Wrong Direction,Phase Current C Wrong Direction ,4 ~ 6 said Phase Current A Wrong
Connecting,Phase Current B Wrong Connecting,Phase Current C Wrong Connecting.