EasyManua.ls Logo

AccuEnergy AcuRev 1300 - Page 88

AccuEnergy AcuRev 1300
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80
AcuRev 1300
40AH 1034
TOU auto reset xed
date: hour (default is
0)
Word R/W 0-23 0 2~4 1
40BH 1035 TOU Enable Word R/W
0: disable; 1:
enable
0 2~4 1
40CH 1036 TOU Settings Number Word R/W
0: System
Setting
1:
Communication
0 2~4 1
40DH 1037
Current number of
taris to congure
Word R/W
1-4
Only can change
when TPU
Tari Number
is set as 1,
Communication
1 2~4 1
40EH 1038
TOU Settings - reset to
factory default
Word W Only “0x0A Valid 2~4 1
TOU Schedule Parameters
420H-
422H
1056-
1058
Time Zone 1: starting
Month, Day, schedule
Table number
R/W 02-01 01 2~4 3
423H-
425H
1059-
1061
Time Zone 2: starting
Month, Day, schedule
Table number
R/W 06-01 02 2~4 3
426H-
428H
1062-
1064
Time Zone 3: starting
Month, Day, schedule
Table number
R/W 10-01 03 2~4 3
429H-
42BH
1065-
1067
Time Zone 4: starting
Month, Day, schedule
Table number
R/W 00-00 00 2~4 3
42CH-
42EH
1068-
1070
Time Zone 5: starting
Month, Day, schedule
Table number
R/W 00-00 00 2~4 3
42FH-
431H
1071-
1073
Time Zone 6: starting
Month, Day, schedule
Table number
R/W 00-00 00 2~4 3

Table of Contents