Page #36 background imageLoading...
Page #36 background image
Cable Assembly
USB Plug
To Wireless
Adapter
Connected System Controller
Figure28: Connecting the Wireless Adapter to the Controller’s USB HOST Port
Configuring the Controller
Any of the following methods can be used to connect to the controller’s interface in order to configure it:
£ Using the controller’s factory-default Hostname in the Web browser
£ Using the controller’s IP address in the Web browser
Default Credentials
If this is a first-time connection to an ECLYPSE controller, or if the controller has been reset to factory default settings, you
must use the default username and password.
Default username:admin
Default password: admin
Using the Controller's Factory-default Hostname in the Web Browser
Controllers have a factory-default hostname that you can use instead of an IP address to connect to it. The hostname can
be used in a Web browser’s address bar. The Bonjour service must be installed on your PC to allow your PC to discover
controllers by their hostname.
If your PC is unable to resolve the controller’s hostname, you must connect your PC to the controller through Ethernet or
Wi-Fi so that your PC only sees the controller network. For example, in this case, your PC must be disconnected from all
other networks such as a corporate network or the Internet. If necessary, temporarily disconnect your PC’s network cable
from its Ethernet port.
The controller’s factory-default hostname is
eclypse-xxxxxx.local
where
xxxxxx
is the last 6 characters of the MAC address
printed on a sticker located on the side of the controller. See Controller Identification.
For example, the sticker on the side of a controller shows that its MAC address is 76:a5:04:cd
:4a:d1. Connect to the con-
troller’s Web interface as follows:
1. Open your Web browser.
2. In the Web browser’s address bar, type https://nLight ECLYPSE-cd4ad1.local and click Go.
3. Log in to the controller. Then set the controller’s configuration parameters in the controller’s configuration Web inter-
face. See Connecting to the Controller's Configuration Web Interface.
The Hostname can be changed in the System Settings.
Using the Controller's IP Address in the Web Browser
Connect to a controller through its IP address as follows:
First Time Connection to an ECLYPSE Controller
36
nLight ECLYPSE

Table of Contents

Other manuals for Acuity Controls nLight ECLYPSE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Acuity Controls nLight ECLYPSE and is the answer not in the manual?

Acuity Controls nLight ECLYPSE Specifications

General IconGeneral
BrandAcuity Controls
ModelnLight ECLYPSE
CategoryController
LanguageEnglish