BACnet Settings
This is where the BACnet interface parameters are set.
General
This sets the controller’s BACnet network parameters.
Figure36: General BACnet Settings
Item Description
Controller Name Set a descriptive name by which this controller will be known to other BACnet objects.
Device ID Each controller on a BACnet intra-network (the entire BACnet BAS network) must have a unique Device ID.
Location Current controller’s physical location. This is exposed on the BACnet network as a device object property.
Description Description of the controller’s function. This is exposed on the BACnet network as a device object property.
APDU Timeout (ms)
Maximum amount of time the controller will wait for an acknowledgment response following a confirmed request sent to a
BACnet device before re-sending the request again or moving onto the next request. This property is exposed on the
BACnet network as a device object property.
APDU Segment Timeout
(ms)
Maximum amount of time the controller will wait for an acknowledgment response following a confirmed segmented
request sent to a BACnet device before re-sending the segmented request again or moving onto the next request. This
property is exposed on the BACnet network as a device object property.
APDU Retries
Sets the number of times to retry a confirmed request when no acknowledgment response has been received. This
property is exposed on the BACnet network as a device object property.
Export BACnet Object List Export all controller BACnet variables to a file (.csv).
Click to refresh the information in the list.
Apply Click
Apply
to apply and save the changes