4-60 ADS TRITON+
®
Manual
DAC Gain Choose the method for managing the
amplification of the analog signal that returns to the
sensor:
Auto Select this option to allow the monitor to
automatically optimize the amplification of the signal.
Manual Select this option to enter a fixed value
between -12db (lower amplification) and +12db (high
amplification) at which to amplify the signal.
Ping Amplitude Choose the method for managing the
amplification of the analog signal that is sent out, or
transmitted from, the sensor. Smaller pipes typically
require weaker (quieter) amplification; larger pipes
typically require stronger (louder) amplification.
Auto Select this option to allow the monitor to
automatically optimize the amplification of the signal.
Manual Select this option to enter the percentage of
full amplification at which to transmit the signal.
Enter a percentage between 10 and 100 percent, where
100 percent represents maximum amplification.
Temperature tab AV|Max/Peak Combo
The temperature sensor measures the temperature of the flow at the
location at which the sensor is installed. The temperature is logged
at the same interval as the other entity data. The Peak Combo
Sensor uses temperature data to calculate the speed of sound in
water.