Troubleshooting
61287722G1-5B 41
UPS Communication Signals
ThecommunicationsignalsoftheUPSareisolatedfromtheinternalcircuitryviaopen
collectoroptocoupledtransistors.Theconnection
SIG RTN(SignalReturn)isacommon
returnpointforallcommunicationsignals.Inthetypicalapplication,theattachedequipment
digitalgroundconnectstoSignalReturn,andpullupresistorsturntheopencollectorsignals
intologiclevels.
ApinoutofthecommunicationsignalsisshowninTable13.
Table 13. UPS Communication Signal Descriptions
Signal Description
+12VDC Vo+(+Voltageoutput)
12VRTN Returnpathfor+12VDC
SIGNALRETURN Signalreturn
ONBATTERY Lowwhenoperatingfromutilityline
Openwhenoperatingfrombattery
REPLACEBATTERY Lowwhenbatteryischarged
Openwhenbatteryfailsselftest
BATTERYMISSING Lowwhenbatteryispresent
Openwhenbatteryismissing
LOWBATTERY Lowwhenbatteryisnearfullcharg
ecapaci
ty
Openwhenoperatingfromabatterywithlessthan20%capacity