EasyManuals Logo

Aerco Benchmark 2000 User Manual

Default Icon
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #121 background imageLoading...
Page #121 background image
Benchmark 1500 - 2000 Boilers
CHAPTER 9. BOILER SEQUENCING TECHNOLOGY
OMM-0097_0E AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 121 of 182
GF-142 Ph.: 800-526-0288 10/01/2015
Option 3 Continued
Step 3 - Configure ALL C-More Units
On ALL Boilers:
1. Go to the Configuration menu item and set the BST Menu item to Enabled.
2. Go to the Boiler Sequencing Menu item and set the BST Mode item to BST Slave (for now).
On MASTER only:
3. Go to the BST Setpoint item and enter the Failsafe Setpoint.
4. Go to the BST Setup Menu item and set to Enabled.
5. Go to the BST Setpoint Mode item and select Outdoor Reset.
6. Go to the Head Temp Source item and select FFWD Temp.
7. Go to the BST Outdoor Sens item and select Enabled.
8. Go to the Outdoor Temp Source item and select Outdoor Temp.
When ALL C-More units have been configured:
9. Go to the Boiler Sequencing Menu item of the desired Master unit and set the BST Mode item to
BST MASTER.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aerco Benchmark 2000 and is the answer not in the manual?

Aerco Benchmark 2000 Specifications

General IconGeneral
BrandAerco
ModelBenchmark 2000
CategoryBoiler
LanguageEnglish

Related product manuals