EasyManuals Logo

Aerco Benchmark 2000 User Manual

Default Icon
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
Benchmark 1500 - 2000 Boilers
CHAPTER 2 INSTALLATION
Page 30 of 182 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0097_0E
10/01/2015 Ph.: 800-526-0288 GF-142
NOTE
If the Valve Feedback option is used, Shorting Jumper #JP2 on the I/O
Board MUST be inserted.
2.10.7 SHIELD Terminals (SHLD & SHLD)
The SHIELD terminals are used to terminate any shields used on sensor wires connected to the
unit. Shields must only be connected to these terminals.
2.10.8 ANALOG OUT Terminals
The ANALOG OUT terminals (+ & -) output from 0 to 20 mA and may be used to monitor
Setpoint, Outlet Temperature, Valve Position 4-20 mA, Valve Position 0-10v or be set to OFF.
Default setting in the C-More controller is Valve Position 0-10v and settings behave as follows:
1. When 0-10VDC is selected, the voltage output is used by the controller to modulate the
combustion blower via the I/O Box terminals labeled VFD/Blower (Section 2.10.11).
2. If On Board Boiler Sequencing Technology (BST) is enabled, the Analog Output
terminals are used to drive the isolation valve, open and closed.
NOTE
When driving an isolation valve, shorting jumper #JP2 on the I/O
Board MUST be installed.
3. When the 4-20mA is selected for the Analog Output, the 0-10VDC is disabled at the
VFD/Blower terminals, and the selected output is available at the terminals labeled
Analog Output +/-.
2.10.9 RS485 Comm (+, GND, & -)
The RS485 communication terminals are used when the boiler plant is being controlled by an
Energy Management System (EMS) or an AERCO Control System (ACS) using Modbus
(RS485) communication.
2.10.10 RS232 Comm (TxD & RxD)
As of Firmware version 4.0 and above, these terminals are used only by factory-trained
personnel to monitor OnAER communications via a portable computer.
2.10.11 VFD/Blower (0-10 & AGND)
These terminals (0-10 & AGND) send an analog signal to control the blower speed. When any
of the 4-20mA options is selected for the Analog Outputs (Section 2.10.8), the output from the
VFD/Blower terminals is disabled.
2.10.12 Interlocks
The unit offers two interlock circuits for interfacing with Energy Management Systems and
auxiliary equipment such as pumps or louvers or other accessories. These interlocks are called
the Remote Interlock and Delayed Interlock (REMOTE INTL’K IN and DELAYED INTL’K IN in
Figure 2-12). Both interlocks, described below, are factory wired in the closed position (using
jumpers).
NOTE
Both the Delayed Interlock and Remote Interlock must be in the
closed position for the unit to fire.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aerco Benchmark 2000 and is the answer not in the manual?

Aerco Benchmark 2000 Specifications

General IconGeneral
BrandAerco
ModelBenchmark 2000
CategoryBoiler
LanguageEnglish

Related product manuals