Benchmark 1500 - 2000 Boilers
CHAPTER 3 OPERATION
Page 44 of 182 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0097_0E
10/01/2015 Ph.: 800-526-0288 GF-142
Table 3-4: Configuration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
19
Low Fire Timer 2 sec. 600 sec. 2 sec.
20
Setpt Limiting Enabled or Disabled Disabled
21
Setpt Limit Band
0°F (0°C) 10°F (5.5°C) 5°F (2.75°C)
22
Network Timeout 5 sec. 999 sec. 30 sec.
23
Shutoff Dly Temp
0°F (0°C) 25°F (13.75°C) 10°F (5.5°C)
24
Demand Offset
0°F (0°C) 25°F (13.75°C) 0°F (0°C)
25
Deadband High
0°F (0°C) 25°F (13.75°C) 5°F (2.75°C)
26
Deadband Low
0°F (0°C) 25°F (13.75°C) 5°F (2.75°C)
27
IGST Version
V2.00 or Lower
V2.02
28 IGN Time Setting 4 sec. 7 sec.
29 Slow Shutdown Enabled or Disabled Disabled
30 Slow Sht Duration 0 sec. 9,999 sec. 60 sec.
31
Slow Sht Threshold 40% 100% 60%
32 BST Menu Enabled or Disabled Disabled
*NOTE
The Bldg Ref Temp and Reset Ratio menu Items are only
displayed when the Outdoor Sensor menu item is set to Enabled.
CAUTION
DO NOT change the Analog Output menu item from its default
setting (Valve Position 0-10V).