6–5Install and Wire the Clutch/Brake Control System
Publication
65566.5.1 - October 1996
1771ID16 Input Modules
These modules have an input filter with a configurable time constant.
It is factory set to the faster response time. Leave jumpers JPR1 and
JPR2 in their factory-set position. If you need additional
information, refer to the Product Data publication 1771-2.189.
Install processors and modules in designated slots of chassis A
(Figure 6.4) and chassis B (Figure 6.5) as follows:
Slot Chassis A Chassis B
PLC5/46 PLC5/26
0, 1 Reserved for your use Reserved for your use
24 Isolated Input Module 1771ID16 Isolated Input Module 1771ID16
5 Isolated Output Module 1771OD16 Isolated Output Module 1771OD16
6 Reserved for your use Reserved for your use
7 Slot Power Supply 1771P4S Slot Power Supply 1771P4S
Figure 6.4
Module
Locations in Chassis A
1771
ID16
1771
ID16
1771
ID16
1
2
1
2
PLC5/46
0 1 2 3 4 5
1771
OD16
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
6 7
1771
P4S
Install PLC Processors,
I/O Modules, and
Power Supplies