112 Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Chapter 6 Develop Safety Applications
Produce a Safety Tag
Follow this procedure to produce a safety tag.
1. In the producing controllers project, create a user-defined data type
defining the structure of the data to be produced.
Make sure that the first data member is of the
CONNECTION_STATUS data type.
2. Right-click Controller Tags and choose New Tag.
3. Set the type as Produced, the class as Safety, and the Data Type to the
user-defined type you created in step
1.
4. Click Connection and enter the number of consumers.
5. Click Advanced if you want to change the type of connection by
unchecking āAllow Unicast Consumer Connectionsā.
6. Click OK.