120 Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Chapter 6 Develop Safety Applications
You can safety-lock and -unlock the controller from the Safety tab of the
Controller Properties dialog box, or by choosing Tools>Safety>Safety Lock/
Unlock.
Figure 27 - Safety-locking the Controller
If you set a password for the safety-lock feature, you must type it in the Enter
Password field. Otherwise, click Lock.
You can also set or change the password from the Safety Lock dialog box. See
page
51.
The safety-lock feature, described in this section, and standard security
measures in the Logix Designer application are applicable to GuardLogix
controller projects.
Refer to the Logix5000 Controllers Security Programming Manual,
publication
1756-PM016, for information on Logix Designer security features.
Generate a Safety Task Signature
Before verification testing, you must generate the safety task signature. You can
generate the safety task signature only when online with the safety-unlocked
GuardLogix controller in Program mode, and with no safety forces, pending
online safety edits, or safety faults. The safety status must be Safety Task OK.
In addition, you cannot generate a safety task signature if the controller is in
Run mode with run mode protection enabled.
TIP You can view the safety status via the safety status button on the online bar
(see page
142) or on the Safety tab of the Controller Properties dialog box,
as shown on page
121.