Rockwell Automation Publication 1756-UM022D-EN-P - May 2017 31
Install the Controller Chapter 2
5. Close the SD card door.
Make Communication
Connections
The controller has a USB port that uses a Type B receptacle. The connection is
USB 2.0-compatible and runs at 12 M.
To use the USB port of the controller, you must have RSLinx® software, version
2.59 or later, installed on your workstation. Use a USB cable to connect your
workstation to the USB port. With this connection, you can update firmware
and download programs to the controller directly from your workstation.
Figure 3 - USB Port
Log
ix 55
xx
RUN
FORCE
SD
OK
32006-M
ATTENTION: Use the USB port for temporary local programming
purposes. Do not use the USB port as a permanent connection.
The USB cable must not exceed 3.0 m (9.84 ft) and must not contain hubs.
WARNING: Do not use the USB port in hazardous locations.