EasyManua.ls Logo

Allen-Bradley GuardLogix 5570

Allen-Bradley GuardLogix 5570
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Chapter 1 System Overview
Select Communication
Networks
The GuardLogix controller supports communication that lets it do the
following:
Distribute and control Safety I/O on DeviceNet or EtherNet/IP
networks
Distribute and control remote Safety I/O on DeviceNet, EtherNet/IP,
or ControlNet networks
Produce and consume safety tag data between 1756 and 1768
GuardLogix controllers across EtherNet/IP or ControlNet networks or
within the same ControlLogix chassis
Distribute and control standard I/O on Ethernet, ControlNet, or
DeviceNet networks
Use these communication modules to provide an interface between
GuardLogix controllers and network devices.
The GuardLogix controller can connect to the Logix Designer application via
a USB port, an Ethernet module, or a ControlNet module.
See
Additional Resources on page 11 for more information on network
communication modules.
Table 6 - Communication Modules
To interface between Use this module See these installation
instructions
The GuardLogix controller and DeviceNet
devices
1756-DNB
DNET-IN001
The GuardLogix controller and EtherNet/IP
devices
1756-ENBT
1756-EN2T
1756-EN2F
1756-EN2TR
1756-EN3TR
1756-EN2TXT
1756-EN2TRXT
ENET-IN002
Controllers on the ControlNet network
1756-CN2
1756-CN2R
1756-CN2RXT
CNET-IN005