40 Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Chapter 2 Install the Controller
When the upgrade is complete, click OK on the Who Active dialog box.
Choose the Operating Mode
of the Controller
Use this table as a reference when determining your controller Operation
mode.
WARNING: Let the firmware update to fully complete before cycling power
or otherwise interrupting the upgrade.
TIP If the ControlFLASH upgrade of the controller is interrupted, the controllers
revert to boot firmware, that is firmware revision 1.xxx.
Table 14 - Controller Operation Modes
If you want to
Select one of these modes
Run
Remote
Program
Run Test Program
Turn outputs to the state commanded by the logic of
the project
XX
Turn outputs to their configured state for Program
mode
XX X
Execute (scan) tasks XXX
Change the mode of the controller through software XX X
Download a project XX X X
Schedule a ControlNetâ„¢ network XX
While online, edit the project XX X X
Send messages XXX
Send and receive data in response to a message from
another controller
XXX X X
Produce and consume tags XXX X X