EasyManua.ls Logo

Allen-Bradley GuardLogix 5570

Allen-Bradley GuardLogix 5570
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 1756-UM022D-EN-P - May 2017 75
Chapter 5
Add, Configure, Monitor, and Replace
CIP Safety I/O Devices
For more information on installation, configuration, and operation of safety
I/O devices, refer to
Additional Resources on page 11.
Add Safety I/O Devices
When you add a safety I/O device to the system, you must define a
configuration for the device, including the following:
Node address for DeviceNet™ networks
You cannot set the node address of a safety I/O device on DeviceNet
networks via the Studio 5000 Logix Designer® application. Node
addresses are set via rotary switches on the devices.
IP address for EtherNet/IP™ networks
To set the IP address you can adjust the rotary switches on the device;
use DHCP software (available from Rockwell Automation); use the
Logix Designer application; or retrieve the default address from
nonvolatile memory.
Safety network number (SNN)
See page
79 for information on setting the SNN.
Topic Page
Add Safety I/O Devices 75
Configure Safety I/O Devices 76
Set the IP Address by Using Network Address Translation (NAT) 78
Set the Safety Network Number (SNN) 79
Use Unicast Connections on EtherNet/IP Networks 79
Set the Connection Reaction Time Limit 79
Understanding the Configuration Signature 85
Reset Safety I/O Device Ownership 86
Address Safety I/O Data 86
Monitor Safety I/O Device Status 88
Reset a Module to Out-of-box Condition 89
Replace a Device by Using the Logix Designer Application 90
Replace a POINT Guard I/O Module by Using RSNetWorx for DeviceNet Software 97

Table of Contents

Other manuals for Allen-Bradley GuardLogix 5570

Related product manuals