Rockwell Automation Publication 1756-UM022D-EN-P - May 2017 23
Install the Controller Chapter 2
Table 13 - North American Hazardous Location Approval
The following information applies when operating this equipment in
hazardous locations.
Informations sur l'utilisation de cet équipement en environnements
dangereux.
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in
Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a
system, the most adverse temperature code (lowest T” number)
may be used to help determine the overall temperature code of the
system. Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the time
of installation.
Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne conviennent qu'à
une utilisation en environnements de Classe I Division 2 Groupes A, B,
C, D dangereux et non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent le code de
température pour les environnements dangereux. Lorsque plusieurs
produits sont combinés dans un système, le code de température le
plus défavorable (code de température le plus faible) peut être utilisé
pour déterminer le code de température global du système. Les
combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de
l'installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power has
been removed or the area is known to be
nonhazardous.
Do not disconnect connections to this equipment
unless power has been removed or the area is
known to be nonhazardous. Secure any external
connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or
other means provided with this product.
Substitution of components may impair
suitability for Class I, Division 2.
If this product contains batteries, they must only
be changed in an area known to be
nonhazardous.
AVERTISSEMENT: RISQUE D’EXPLOSION
Couper le courant ou s'assurer que l'environnement
est classé non dangereux avant de débrancher
l'équipement.
Couper le courant ou s'assurer que l'environnement
est classé non dangereux avant de débrancher les
connecteurs. Fixer tous les connecteurs externes
reliés à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres moyens
fournis avec ce produit.
La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non
dangereux avant de changer les piles.