64 Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Chapter 4 Communicate over Networks
2. Click Copy.
3. Click OK to close the dialog box.
4. Click the General tab on the Module Properties dialog box of the I/O
device in the I/O Configuration tree of the consuming controller
project.
This consuming controller is not the configuration owner.
5. Click to the right of the safety network number to open the Safety
Network Number dialog box.
6. Click Paste.
7. Click OK.