Rockwell Automation Publication 1756-UM022D-EN-P - May 2017 95
Add, Configure, Monitor, and Replace CIP Safety I/O Devices Chapter 5
Scenario 3 - Replacement Device SNN Is Different from Original and No Safety Signature
Exists
1. Remove the old I/O device and install the new device.
2. Right-click your safety I/O device and choose Properties.
3. Click the Safety tab.
4. Click Reset Ownership.
5. Click OK.
6. Follow your company-prescribed procedures to functionally test the
replaced I/O device and system and to authorize the system for use.