EasyManua.ls Logo

Allen-Bradley SLC 500 Series - Page 281

Allen-Bradley SLC 500 Series
694 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1747-RM001G-EN-P - November 2008
SLC Communication Instructions 12-15
Message Timeout for any SLC 5/05 channel 1 MSG cannot be modified
in the Ethernet Message Setup dialog box. It is assigned by the
processor and is determined by adding the Channel 1 MSG Connection
Timeout to the MSG Reply Timeout, then adding five seconds. This
value can be modified by changing one or both of the timeout values in
the channel 1 channel configuration screen. The modified message
timeout applies to all MSG instructions.
Data Table Address
(1)
For a Read, this is the starting address where the data is being read
from.
For a Write, this is the starting address where the data is being written
to.
To enter in a PLC-5 type logical ASCII address, begin the address
name with a $ and enclose the name in double quotes (example:
‘$N7:0’). To enter in a PLC-5 type symbolic address, enclose the
name in double quotes (example: ‘READ_TAG’).
Data Table Offset
(2)
Specifies the word offset into an SLC 500 or MicroLogix Common
Interface File (CIF) or byte offset into a PLC-5 or Logix PLC-2
compatibility file. Valid range is 0 to 255.
Local Node Addr (dec)/(oct)
(3)
(4)
(1)
500 CPU and PLC-5 Target Devices only.
TIP
You may use the PLC-5 type symbolic address to
read/write controller tags in Logix controllers. The
supported address forms are:
tag_name.
tag_name[x].
tag_name[x,y] or tag_name[x][y].
tag_name[x,y,z] or tag_name[x][y][z].
Use INT data type for integer files or REAL data type for
floating point files.
(2)
485 CIF Target Devices only.
(3)
Local MSG only.
(4)
All processors except SLC 5/05 Channel 1.

Table of Contents

Other manuals for Allen-Bradley SLC 500 Series

Related product manuals