Publication 1747-RM001G-EN-P - November 2008
Programming Instruction References D-13
MSG
(5/03, 5/04, and
5/05
(7)
)
Message type 64=peer-to-peer
read/write 0=read, 1=write
target device 2=500CPU,
4=485CIF, 8=PLC5
local/remote 16=local,
32=remote
control block direct N none
control block
length
14
(8)
channel number 5/03 and 5/04: 0
or 1
5/05: 0 only
target node 0 to 31,
0 to 254 if 485CIF
remote bridge link
ID
0 to 254, 0 when
local
remote bridge
node address
0 to 254, 0 when
local
local bridge node
address
0 to 254,
0xFFFF when local
local file address direct O, I, S, B, T, C, R, N,
F, A, ST, M
(9)
none
target file address direct O, I, S, B, T, C, R, N,
F, A, ST, M
(9)
0 to 255
message length
O, I, B, N, A
(9)
1 to 103
S
(9)
5/03 and 5/05: 1
to 83
5/04: 1 to 164
F
(9)
1 to 51
T 1 to 34 (if PLC5: 1
to 20)
C, R 1 to 34
ST
(9)
2 (if PLC5: 1)
message timeout 0 to 255 (SLC
5/05-23 seconds,
read only)
Table D.3 Available Addressing Modes (Continued)