EasyManua.ls Logo

Allen-Bradley SLC 500 Series - Capturing M0-M1 File Data; Specialty IO Modules with Retentive Memory

Allen-Bradley SLC 500 Series
694 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1747-RM001G-EN-P - November 2008
E-24 Data File Organization and Addressing
Capturing M0-M1 File Data
The first two ladder diagrams in the last section illustrate a technique allowing
you to capture and use M0 or M1 data as it exists at a particular time. In the
first figure, bit M0:2.1/1 could change state between rungs 1 and 2. This could
interfere with the logic applied in rung 2. The second figure avoids the
problem. If rung 1 is true, bit B3/10 captures this information and places it in
rung 2.
In the second example of the last section, a COP instruction is used to
monitor the contents of an M1 file. When the instruction goes true, the 6
words of data in file #M1:4.3 is captured as it exists at that time and placed in
file #N10.0.
Specialty I/O Modules with Retentive Memory
Certain specialty I/O modules retain the status of M0-M1 data after power is
removed. See your specialty I/O module user’s manual. This means that an
OTE instruction having an M0 or M1 address remains on if it is on when
power is removed. A “hold-in” rung as shown below will not function as it
would if the OTE instruction were non-retentive on power loss. If the rung is
true at the time power is removed, the OTE instruction latches instead of
dropping out; when power is again applied, the rung is evaluated as true
instead of false.
You can achieve non-retentive operation by unlatching the retentive output
with the first pass bit at powerup.
ATTENTION
When used with a specialty I/O module having
retentive outputs, this rung can cause unexpected
start-up on powerup.

Table of Contents

Other manuals for Allen-Bradley SLC 500 Series

Related product manuals