Rockwell Automation Publication 1783-UM007G-EN-P - February 2017 175
Install Stratix 8000 and 8300 Switches Chapter 6
3. Use an 18-gauge wire-stripping tool to strip each of the two wires to
6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.).
Do not strip more than 6.8 mm (0.27 in.) of insulation from the wire.
Stripping more than the recommended amount of wire can leave
exposed wire from the connector after installation.
4. Insert the exposed part of the positive wire into the DC + connection
and the exposed part of the return wire into the DC - connection.
5. Make sure that you cannot see any wire lead; only wire with insulation
can extend from the connector.
6. Use a ratcheting-torque screwdriver to torque the power connector
captive screws above the installed wire leads to 0.23 N•m (2.0 lb•in).
7. Connect the other end of the positive wire (the one connected to DC +)
to the positive terminal on the DC power source, and connect the other
end of the return wire (the one connected to DC -) to the return
terminal on the DC power source.
31784-M
6.8 mm (0.27 in.)
32436-M
DC -
DC +