Rockwell Automation Publication 1783-UM007G-EN-P - February 2017 77
Install Stratix 5400 Switches Chapter 3
Obtain these tools:
• Ratcheting torque screwdriver that exerts up to 1.69 N
•m (15 in•lbs) of
pressure
• Small, flat-blade screwdriver
• #6 ring terminal lug for 5.3 mm

(10 AWG) wire, such as Thomas &
Bett part number 10RC6 or equivalent
• Crimping tool, such as Thomas & Bett part number WT2000,
ERG-2001, or equivalent
• 5.3 mm
2
(10 AWG) copper ground wire, such as Belden part number
9912 or equivalent
• Wire-stripping tool
• For panel-mounting without a DIN rail, M5 or #10-24 or #10-32 bolts
or screws with 1.27 cm (0.5 in.) O.D. flat washers
For simplified cabling, the automatic medium-dependent interface crossover
(auto-MDIX) feature is enabled by default on the switch. With auto-MDIX
enabled, the switch detects the required cable type for copper Ethernet
connections and configures the interfaces accordingly. Therefore, you can use
either a crossover or a straight-through cable for connections to a 10/100 or
10/100/1000 Ethernet switch port, regardless of the type of device on the
other end of the connection.