SECTION 9 – TROUBLESHOOTING
PAGE 9-4 REV. 0 2014-APR-30
CHECKFIRE 110
Detection and Actuation System
TABLE 9-4: MULTIPLE CIRCUIT FAULTS
Multiple Circuit Faults
Detection Circuit Fault, Release Circuit Fault, “PUSH to
Activate / Alarm When Lit” LEDs, and Sounder pulsing 1 x
10 seconds indicate Post Discharge Mode, Detection Circuit
fault, and/or Release Circuit fault.
When multiple fault conditions exist, check each circuit as 
previously described (clear circuit faults in this order: Power,
Release, Detection). Determine fire system status.
•  Check connections on all cables
•  Check Release Circuit Cables for an open circuit or a 
ground fault; replace cables as needed
•  Check Detection Circuit Cables for an open circuit or a 
ground fault; replace cables as needed
•  Check for activated or missing PAD(s); replace as needed 
following Section 8 – Recharge instructions
Note: The Power LED could also be pulsing AMBER if there
is a fault in the External Power Circuit.
TABLE 9-5: SPECIFIC CIRCUIT TESTING PROCEDURES
General Instructions
Test the connecting cables if faults are indicated on the
CHECKFIRE 110 Control Module, and end of circuit devices
(EMAs, EOL Device, branch terminators, PADs, etc.) are
properly connected to the system.
Before testing specific circuits, confirm completion of a thor-
ough visual inspection. Inspect all cables for damage and
replace if there are visible and mechanical signs of damage
(brittleness, deformation, discoloration, etc.). Test all connec-
tions for loose or disassembled connectors.
Note: Once all faults are cleared, confirm proper operation of
the entire CHECKFIRE 110 System by completing Section 6 -
Test and Place in Service.
If faults cannot be cleared, test each circuit and cable individ-
ually with the following procedures.
009180b
MULTIPLE
CIRCUIT FAULTS
ALL LEDS
PULSING
1 X 10 SECONDS
!
!

Table of Contents

Other manuals for Ansul CHECKFIRE 110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul CHECKFIRE 110 and is the answer not in the manual?

Ansul CHECKFIRE 110 Specifications

General IconGeneral
BrandAnsul
ModelCHECKFIRE 110
CategoryControl Systems
LanguageEnglish

Related product manuals