Chapter 3: Configuration and commissioning
42 1X-X3 Installation Manual
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter
4. Save your changes.
The available settings for this feature are shown below.
Display Description
Actuator delay applies to the MCP Start.
MCP Start activates the actuator immediately (no delay).
Extinguishing agent flow
Use this menu to configure how the control panel enters into the extinguishing
released state: using extinguishing agent flow confirmation or immediately after
the activation of the actuator.
The default setting does not use extinguishing agent flow confirmation:
extinguishing agent flow OF. Note that with this configuration the control panel
continues to provide indications of the extinguishing agent flow for information
purposes (wiring faults and activation).
If your installation requires an extinguishing agent flow signal, see āConnecting
an extinguishing agent flow deviceā on page 12 for more information.
To configure extinguishing agent flow:
1. Set the display as shown below, and then press Enter.
The red Released LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display Description
Extinguishing released after extinguishing agent flow
input activation.
Extinguishing released after actuator activation.
(Extinguishing agent flow indications available for
information purposes)