Chapter 3: Configuration and commissioning
54 1X-X3 Installation Manual
Response times
Response times for standard events are as follows.
Table 14: Response times for standard events
Event Response time
Alarm Less than 3 seconds
Input activation Less than 3 seconds
MCP Hold fault Less than 2 seconds
MCP Abort fault Less than 2 seconds
Other input faults Less than 3 seconds
Actuator fault Less than 30 seconds
Optical panel fault Less than 30 seconds
Zone fault Less than 30 seconds
Sounder fault Less than 30 seconds
Fire routing fault Less than 30 seconds
Earth fault Less than 100 seconds
Battery charger fault Less than 100 seconds
No batteries found fault Less than 3 minutes
Mains fault Less than 3 minutes
Low battery fault Less than 100 seconds
Fuse/protection fault Less than 3 minutes
System fault Less than 100 seconds
Battery high resistance fault Less than 4 hours