Unit Configuration
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 96
5.13.6 VDR
This menu selection allows you to define all settings for the Voyage
Data Recorder (VDR), including the following submenus:
Configure Settings (chapter 5.13.6.1)
Send Test Event (chapter 5.13.6.2)
Note that the Voyage Data Recorder (VDR) requires the use of the
serial port.
5.13.6.1 Configure Settings
This menu selection allows you to configure VDR settings.
From the External Interfaces Menu (5.13.1), perform the
following:
Use the arrow down button to select VDR, then press Enter.
Select Configure Settings (the uppermost selection), then press
Enter twice.
Type a new Name, or accept the existing one by pressing the
arrow down button.
Press Enter, use the arrow left/right buttons to select the port
(not in use or serial), then press Enter.
Use the arrow left/right buttons to select whether you want to
restore factory settings or not (Yes/No), then press Enter.
Use the arrow left/right buttons to select Log Volume Mini
(Yes/No), then press Enter.
If Yes is selected, the amount of information which is sent to the
VDR will be limited; only information on alarms and door control
will be sent.
Use the arrow left/right buttons to select Alive Time (default 4
minutes), then press Enter.
Alive Time determines how often a message is sent to the
VDR to ensure that there is a proper communication between the
system and the VDR.
Use the arrow left/right buttons to select Update Time
(default 120 minutes), then press Enter.
Update Time determines how often the VDR receives a full
update of all fire alarms and fault statuses.
To confirm the settings, press Enter once more.
5.13.6.2 Send Test Event
This command is used for test purposes.
From the External Interfaces Menu (5.13.1), perform the
following:
Use the arrow down button to select VDR, then press Enter.
Use the arrow down button to select Send Test Event, then press
Enter
The following message will appear:
“Test message transmitted”.